problem
LED is not lit
No power supply
LED flashes
The power supply collapses periodically -
sporadically white
device software reboots each time
LED flashes red or
The residual ripple of the supply voltage is too
LED illuminates red
high
Temperature too high
Standard signal is < 4 mA; cable break
Valve opens even
Operating direction of the set-point value has
though it should
been set incorrectly
close
Motor is making an
Gearbox or motor blocked
unusual droning
noise
Valve is not opening
Low power function activated; motor torque
or closing correctly
for medium pressure too low
Valve is not sealed
Dirt between seal and valve seat
16
All manuals and user guides at all-guides.com
possible cause
english
Type 3270, 3275
Maintenance,troubleshooting
remedial action
Check the electrical connections
Select power supply with adequate power
Check cable for possible lose connections
Use power supply with a smooth output voltage at the required
power
After eliminating the fault, restart the device for normal operating
(isolate from power supply)
Observe max. ambient temperature / medium temperature; if
required reduce duty cycle (see Derating curve)
After eliminating the fault, restart the device for normal operating
(isolate from power supply)
Check cable for possible lose connections
Change direction of the input signal
Return device to the manufacturer to have the fault repaired
Deactivate energy save function
Install dirt filter and return device to the manufacturer for cleaning