Gas Supply Pressure
CAUTION
To avoid property damage, maximum gas supply
pressure must not exceed 14" WCP.
• Appliance and individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of ½ psig (3.5kPa) (14" WCP).
• Appliance must be isolated from gas supply piping
system by closing manual shutoff valve during any
pressure testing of the gas supply piping system at
test pressures equal to or less than ½ psig (3.5kPa)
(14" WCP).
• Gas supply pressure for checking regulator setting
must be at least 1" WCP above manifold pressure
shown on rating label.
Pressure Regulator Location
Remove rear cover to expose pressure regulator.
Regulator Cover
All manuals and user guides at all-guides.com
Converting for Use with Natural Gas or
Propane Gas
This range arrives from factory adjusted for use with
natural gas. If using LP/propane gas is desired, range
must be converted. See "Type 1" or "Type 2" regulator.
To avoid electric shock that can cause personal injury
or death, disconnect main electrical supply to range
before servicing.
Converting Type 1 Pressure Regulator for Use with
LP/ Propane
1. Remove pressure regulator cap with a wrench.
2. Remove plastic insert from pressure regulator cap.
• Plastic insert fits tightly in cap.
3. Reverse plastic insert and carefully push plastic
insert firmly into hole in pressure regulator cap.
• Insert must show "LPG10" or "LP10".
4. Place pressure regulator cap on pressure regulator
and tighten.
• Insert should not disturb spring in body of regulator.
A—Cap
B—Plastic Insert (LP setting)
C—Spring Location
Type 1 Pressure Regulator
8
WARNING
B
A
C