Télécharger Imprimer la page

Honeywell GT-530 Manuel De L'utilisateur page 11

Publicité

Les langues disponibles

Les langues disponibles

These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer's requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
60" Minimum
Generator
This drawing supersedes installation instructions in all air-cooled installation and owner's manuals dated previous
to May 26, 2007.
Figure 1.8 – Installation Guidelines
No operable windows or openings in the wall permitted
within 5 feet from any point of the generator.
Existing Wall
60 inches
Minimum Distance
36 inches
Top of Generator
18 inches
36 inches
60" Recommended
Minimum From Ends
General Information
60 inches
Clearance from operable
36 inches
windows, doors, any
openings in the wall,
shrubs or vegetation over
12" in height
Clearance from the ends and front of the
generator must be 36 inches. This would
include shrubs, trees and any kind of
vegetation. Clearance at the top should
be a minimum of 60 inches from any
structure, overhang or projections from
the wall. The generator should not be
placed under a deck or other structure
that is closed in and would limit or
constrain air flow.
18 inches
Minimum
9

Publicité

loading

Ce manuel est également adapté pour:

Gt-990Gt-999