3.4 ELECTRICAL WIRING
WARNING
DO NOT EXCHANGE NEUTRAL
WITH PHASE.
~
230V
N
L
Limit thermostat
with manual
T
resetting
7 pin plug
L1
N
7 pole socket
Ignition
CONTROL BOX
electrodes
550SMD
D6123
Fig. 10
B
A
2330
All manuals and user guides at all-guides.com
50Hz
Switch with fuse
6A max.
Regulating thermostat
T
T1
T2
S3
B4
Black
Blue
Brown
Brown
Blue
Black
White
Blue
Burner-earth
Green led (Fan)
Yellow led (Heater)
Red led
(Lock-out signalling due to
failure to shut-down)
To remove the control-box from the burner, loosen screw (A, fig. 10) after
removing all components, the 7 pin plug and earth wire.
During the re-assembly of the control box, retighten the screw (A) with
a torque wrench setting of 1 – 1.2 Nm.
For burners installed on air generators, remove the bridge (B, fig. 10) from the
E9070
control box.
NOTES:
2
– Wires of 1 mm
– The electrical wiring carried out by the installer must be in
compliance with the rules in force in the Country.
(See page 4). Connect the automatic shut-off device
*
(230V - 0.5A max.) to the clamps N - T2 of the 7 pin plug.
nd
Connect 2
stage thermostat between clamps T6 - T8
by removing the bridge.
TESTING: Check the shut-down of the burner by open-
ing the thermostats and the lock-out by
darkening the photoresistance.
st
1
stage
h
hour counter
(230V - 0.1A max.)
Remote lock-out lamp
(230V - 0.5A max.)
Photoresistance
nd
2
stage oil valve
5
GB
section.
nd
2
stage hour counter
h
(230V - 0.1A max.)
nd
2
stage
T
thermostat
4 pin plug
B5
T6
T7
T8
4 pole socket
st
1
stage oil valve
2 1
3 2 1
ELECTRONIC
DELAYING DEVICE