Télécharger Imprimer la page

Burkert 8681 Démarrage Rapide page 8

Masquer les pouces Voir aussi pour 8681:

Publicité

Les langues disponibles

Les langues disponibles

Current carrying capacity,
sensor power supply: max. 30 mA;
short-circuit protection
Design:
DC 2- and 3-conductor, NO or
NC (factory setting NO), PNP
output
Inputs (from master
perspective):
3 binary feedback signals and
external initiator
Outputs (from master
perspective):
0 to 3 solenoid valves
Switching capacity:
max. 0.8 W via AS interface
Pull-in current:
30 mA or 0.9 W / 200 ms
Operating mode:
Long-term operation (100 %)
Central display of the switching states:
Power consumption: max. 33 mA or 1 W per illumi-
nated display (at 30.5 V AS-
interface voltage)
Power supply via AS interface bus:
Power consumption
from AS interface:
max. 200 mA (incl. external
initiator with 30 mA)
Integrated short-circuit protection
english
28
Pin 2
Pin 3
Likewise, the jumpers on the electronics module must be set
correspondingly (power supply via AS-i or externally) - see
page 27 .
Power supply
(via AS-i)
(externally)
Pin
Confi guration
Confi guration
1
AS-i+
AS-i+
2
not used
GND
3
AS-i-
AS-i-
4
not used
24 V+
An external initiator can be connected using the small
3-pin terminal strip 2 - see manual, chapter „Connection of
an external initiator".
english
30
All manuals and user guides at all-guides.com
Pin 1
Pin 4
Color
brown
white
blue
black
External Power Supply:
Ext. power supply:
Max. power consumption
from external power supply:  110 mA at 24 V DC
Integrated short-circuit protection
10.5.
Electrical Installation (AS-i)
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the
Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-
cians only and with the appropriate tools!
Internal cabling work is not required for any of the AS Interface
designs with multi-pole connection. However, you will require
the correspondingly assembled cable sets with the following
pin assignments.
11. DEVICENET- DESIGN
11.1.
Connection
left connection:
1 x M16 x 1,5 cable gland with Multi-pole connection
(M12 plug according to IEC 61076-2-101, 5-pole) on a
cable of 80 cm length
right connection:
1 x M16 x 1,5 cable gland for external initiator
11.2.
DeviceNet Specifi cation
EDS fi le
8681.EDS
Icons
8681.ICO
Baud rate
Factory setting: 125 kBit/s
Address
Factory setting: 63
Type 8681
19.2 V DC to 31.6 V DC
english
29
english
31

Publicité

loading