6.2.
Structure
Position measuring system with LED's
Electronics module
(24VDC- or AS-i-
Design with service
interface, connection
terminals, DIP, Teach-
In-buttons)
Mechanical
manual control
at solenoid
valves (red
levers)
Electrical
connections
(Cable
glands)
Sealing lug
Locking/(shoulder) screws
as protection against pulling
off from the hub fl ange
english
12
Oil content:
max. 25 mg/m
(quality class 5)
Temperature range
of compressed air:
-10 to +50 °C
Pressure range:
2.5 to 8 bar
Air rate of solenoid
valve:
110 I
/min (for de-/aeration, ventilation)
N
(110 I
/min - supplied state
N
200 I
/min - maximum typical fl ow-rate)
N
(Q
value according to defi nition for
Nn
pressure drop from 7 to 6 bar absolute
at +20 °C)
Connections:
Intake and exhaust air connection G1/4
Working connections
7.4.
Position Measuring System Data
Stroke range:
0 ... 80 mm (measuring range)
0.1 mm
Resolution:
Total fault:
± 0.5 mm - when using a target as
mentioned in the manual
7.5.
Electrical Data
see chapter 9. 24 V DC - Design or 10. AS-I - Design or
11. DeviceNet- Design or 12. 120 V AC - Design .
english
14
All manuals and user guides at all-guides.com
Flow restriction
screw(s) of
solenoid valves
Pneumatic
connections
3
G1/8
7.
TECHNICAL DATA
7.1.
Operating Conditions
Ambient temperature:
-10 ... +55 °C
Protection class: IP65 / IP67 according to EN 60529 or
IP69K according to IEC 40050-9
7.2.
Mechanical Data
Dimensions:
see data sheet
Housing material:
outside:
inside:
Sealing material:
outside:
inside:
7.3.
Pneumatic Data
Control medium:
Oil-free and dry air, neutral gases,
Quality classes in accordance with
DIN ISO 8573-1 (5 µm fi lter
recommended)
Dust content:
max. particle size 40 µm,
(quality class 5)
max. particle density 10 mg/m
Water content:
max. pressure dew point -20 °C or
(quality class 3)
min. 10 °C below the lowest
operating temperature
8.
ASSEMBLY / INSTALLATION
DANGER!
Risk of injury from high pressure in the equipment!
•
Before loosening pneumatic lines and valves, turn off
the pressure and vent the lines.
WARNING!
Risk of injury due to electrical shock!
•
Before reaching into the system (except for the
Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
•
Observe applicable accident prevention and safety
regulations for electrical equipment!
Risk of injury from improper installation!
•
Installation may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
•
Secure system from unintentional activation.
•
Following assembly, ensure a controlled restart.
Type 8681
PA, PP, PPO, VA
ABS, PA, PMMA
CR, EPDM
EPDM, FKM, NBR
3
english
13
english
15