Decommissioning
sensor

12 Repairs

The sensor can be repaired only at the factory. Send it back in its original
packaging. Prepare it for the repairs (as described in Chapter 11
"Decommissioning").

13 Disposal

Electrolyte
The electrolyte and membrane cap can be disposed with domestic waste.
Sensor
®
ProMinent
Decommissioning / Repairs / Disposal
Disconnect the sensor electrically (compare Chapter 7 "Installation").
Depressurise the in-line probe housing.
Screw off the plug of the in-line probe housing.
Slowly pull out the sensor from the in-line probe housing.
Screw off the membrane cap over a sink, empty it and throw it away.
Rinse the electrodes thoroughly in clean, warm water and allow to dry.
Screw on a new membrane cap loosely to protect the electrodes.
Put on the membrane's protective cap.
ATTENTION
Observe the currently valid national regulations.
(especially with regard to electronic waste)