Proceed as described below to connec t the Area T erminal to the Chiller/
heat pump board:
•
remove the panel that protects the elec tric control board;
•
pass the telephone cable c omi ng from the Area Ter minal through
the fairlead pres ent on the str ucture and on the electric c ontrol
board;
•
engage the telephone cable end on the J13 female c onnector
present on the unit circuit board;
•
remount the previ ousl y-removed panels.
Bianco White Blanc Weiss Blanco
1
Nero Black Noir Schwarz Negro
2
Rosso Red Rouge Rot Rojo
3
4
Giallo Yellow Jaune Gelb Amarillo
5
Blu Blue Bleu Blau Azul marino
6
(*) Note: for lengths exceeding 50 m and up to 200 m, the connection
between KTAU and circuit board of the Chiller/heat pump, must be
realised using an AWG 20/22 shielded cabl e (4 wires + screen) and
two by-pass boards (use the E968573484 Kit) as in the layout shown
below.
200 m
6 5 4 3 2 1 0
D
T
AP1
KTAU
J14
J15
1 2 3
1 2 3
C = AWG 20/22 s hielded c abl e (4 wires + screen) (not supplied)
S = Shiel ded cable screen
D = by-pass boar d (E968573484)
T = telephone c able (E968573484)
AP1 = Chiller/heat pump circuit board
1 Rx/Tx-
2 Rx/Tx+
3 GND
4
5
6
C
6 5 4 3 2 1 0
D
T
C
S
6
5
4
3
2
1
II.2.6.2
The connections between board and switc h or remote light must be
made with screened cable (make sure the screening is continuous
throughout the length of the c able) c onsisting of 2 twisted 0.5 mm² wires
and the screening. The screening must be connec ted to the earth scr ew
on the panel (on one side onl y). T he maxi mum permitted distanc e is 30
m.
Lay the c abl es far from power cables, c ables with a different voltage
and cabl es that emit elec tromagnetic distur banc e.
Do not lay the cabl es in the vicinity of appliances that could create
electromagnetic interferenc e.
SCR
SEI
LBG
LFC1
LFC2
LFC3
SDP
CS
• Remote ON/OFF en abling (SCR)
Remove the cl amps jumper and c onnect the wires coming from the
remote c ontrol ON/OFF selec tor (selec tor to be installed by the
installer).
ATTENTION
• Enabling of remote summ er/winter with HPH accessor y
Connect the c ables coming from the remote s ummer/wi nter s elector
onto the clamps .
Now modify the R em. r emote Summ er/W inter param eter (Ref. Page
12).
ATTENTION
• LBG – LCF1 – LCF2 – LCF3 remote control
To remotel y c ontrol the two signals, c onnect the two l amps acc ording to
the i nstructions pr ovided in the wiring diagram supplied with the
mac hine.
0
• Dual set-point manag ement
The DSP acc essor y can be used to connec t a selector in order to
switch between two set-points.
ATTENTION
63
SECTION II: INST ALL ATION AND MAINTEN ANCE
Remote management via set-up for
automated and centralised control system.
Remote c ontrol s elector (contr ol with clean c ontact);
Summer/Winter selec tor onl y with HPH access ory (control
with cl ean contac t);
General loc k light (230 Vac);
Compress or 1 functioni ng light (230 Vac);
Compress or 2 functioni ng light (230 Vac);
Compress or 3 functioni ng light (230 Vac);
Double set-point c onnec tor (DSP access ory), (control with
clean c ontact);
4÷20 mA analogue signal for setting the scrolling set- point
(CS accessor y).
IMPORTANT !
When the unit is switched OFF using the remote
control selector, the message OFF b y digital input
appear s on the control panel display on the
machine.
Open contac t:
Closed c ontact:
Open contac t:
Closed c ontact:
Open contac t:
Closed c ontact:
the unit is OFF.
the unit is ON.
heating cycl e
cooling c ycle
Double Set-point
Set-point