Control Drawings; Kema Approval; (Europe); Factory Mutual Approval (United States) - Mettler Toledo PANTHER Guide D'installation

Masquer les pouces Voir aussi pour PANTHER:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 94
4

KEMA Approval

(Europe)

Factory Mutual
Approval (United
States)

Control Drawings

Only PANTHER panel-mount terminals which are factory-labeled as approved for
Division 2 may be installed into a Division 2 hazardous area.
IN ORDER TO USE THE ANALOG PANTHER PANEL-MOUNT
TERMINAL IN AN AREA CLASSIFIED AS CLASS I, II OR III, DIVISION
2, GROUPS A, B, C, D, F OR G, METTLER TOLEDO CONTROL
DRAWING 155907R MUST BE FOLLOWED WITHOUT EXCEPTION.
FAILURE TO DO SO COULD RESULT IN BODILY HARM AND/OR
PROPERTY DAMAGE.
The PANTHER panel-mount terminal has been submitted to KEMA for certification as
meeting requirements of EN 50021 : 1999, Electrical apparatus for potentially explosive
atmospheres, Type of protection "n" - but the evaluation is not yet complete and a
certificate has not yet been issued.
Until this certificate is issued, the PANTHER panel-mount terminal must not be used in
areas classified as Zone 2 according to harmonized European standards.
The PANTHER panel-mount terminal is NOT approved for Zone 2 applications!
Factory Mutual has evaluated the PANTHER panel-mount terminal and found that it
meets the NEC standards for use in hazardous areas classified as Division 2 when
installed per METTLER TOLEDO control drawing 155907R.
A copy of METTLER TOLEDO control drawing 155907R is shown on the next pages. No
deviation from this drawing is permitted.
Chapter 4: Control Drawings
KEMA Approval
WARNING
(7/03) 4-1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Panther plus

Table des Matières