5.4.1
Schéma 1, gestion de GB
Start
Start DG(s)
No
RPM > SP1
Yes
Close GB
No
RPM > SP2
Yes
Delay 1 expired
on all DG(s)
No
Yes
Start
excitation
DESIGNER'S HANDBOOK 4189341275B FR
No
Yes
Delay 1 expired
Trip GB
No
Yes
Activate
Delay 2 expired
regulators
No
Delay 3 expired
U
No
Yes
"Close before
excitation"
failure
No
Delay 1 expired
Yes
Start
excitation
Delay 2 expired
Yes
Activate
OK
BUS
regulators
Yes
U
OK
BUS
Yes
End
Sync GB
No
No
Delay 3 expired
No
Yes
"Close before
excitation"
failure
Page 93 de 202