5 Construction and function

5.1 Summary
12
6
2
1
3
8
11
9
Illustr. 5.1 Construction with high temperature circuit
Consisting of:
1
Plate heat exchanger
2
Proportional flow controller
3
Thermostatic temperature controller
4
Differential pressure regulator
5
Zone valve for heating circuit control
6
Deaeration heating circuit
7
Spacer for heat meter
8
Spacer for cold water meter
9
Connection facility for temperature sensor for
heat meter M10x1
10 Strainer (with draining facility) heating circuit
return
11 Strainer (with draining facility) heating water
supply
12 Deaeration potable water circuit
13 Check valve mixing function
14 High-efficiency pump
15 Angle pattern valve with thermostat control
heating circuit
16 Contact sensor
17 Stainless steel pipe supply
high temperature circuit
(installation on site)
18 Connection for high
temperature circuit supply
19 T-piece with check valve high
temperature circuit return

5.2 Functional description

The Oventrop dwelling station "Regudis W-HTF"
supplies heat as well as hot and cold potable water
to individual dwellings without using auxiliary heating.
The hot water for heating purposes is provided by a
central heat supply. The potable water is heated locally
via a heat exchanger according to the continuous
flow principle. The control range is adjustable between
40-70 °C.
5
4
Heating operation:
19
Heating water enters the supply of the heating circuit
13
of the dwelling (F) via the supply of the heating system
(D). The proportional flow controller (2) opens the path
between the return of the heating circuit (G) – and the
14
supply return (E).
15
The flow temperature of the heating system is conti-
18
nuously controlled by the contact sensor (16) and the
7
flow volume of the hot fluid is adjusted by the angle
16
pattern valve (15). Depending on the setting of the
angle pattern valve (15), cold water from the return of
10
the heating circuit (G) is added to the heating circuit
17
supply (F) via the check valve (13) (mixing function).
High temperature circuit:
Heating water enters the supply of the high tempera-
ture circuit (I) via the T-piece (18) in the supply (D).
The heating water flows back to the supply return (E)
via the return of the high temperature circuit (H).
Heating of potable water:
The proportional flow controller (2) switches to potable
water priority function, if hot water is demanded in
the dwelling. The heating water of the supply (D)
passes across the plate heat exchanger (1) and the
proportional flow controller (2) and enters the supply
return (E). The cold potable water (C) is warmed up
according to the continuous flow principle and is
available at the hot water supply of the dwelling (A).

6 Installation

Danger to life and limb
Danger to life and limb!
Installation, initial operation, maintenance and re-
pairs must only be carried out by qualified trades-
men (specialist heating company/ authorised com-
pany).
6.1 Installation
Determine installation location and ensure that a pe-
ripheral distance of 100 mm towards any obstruction
High
is guaranteed.
temperature
Install piping according to the connection plan (see
circuit
4.3). All connections must be equipped with isolating
valves (G
to the dimensional sketch (illustr. 4.2). Align station,
mount onto the isolating valves with the supplied seals
and connect using the enclosed fixing material.
DANGER
3
, flat sealing). Drill fixing holes according
4
23