5 Construction and function

5.1 Summary
12
6
2
1
3
8
9
Illustr. 5.1 Construction with constant temperature
circuit
Consisting of:
1
Plate heat exchanger
2
Proportional flow controller
3
Thermostatic temperature controller
4
Differential pressure regulator
5
Zone valve for heating circuit control
6
Deaeration heating circuit
7
Spacer for heat meter
8
Spacer for cold water meter
9
Connection facility of temperature sensor to
heat meter M 10x1

5.2 Functional description

The Oventrop dwelling station "Regudis W-HTF"
supplies heat as well as hot and cold potable water to
individual dwellings without using auxiliary heating.
The hot water for heating purposes is provided by a
central heat supply. The potable water is heated locally
via a heat exchanger according to the continuous flow
principle. The control range is adjustable between
40-70 °C.
Heating water enters the heating circuit of the dwelling
(F) via the supply of the heating system (D). The
proportional flow controller (2) opens the path between
the return of the heating circuit (G) and the supply
return (E).
Heating of potable water:
The proportional flow controller (2) switches to potable
water priority function, if hot water is demanded in
the dwelling. The heating water of the supply (D)
passes across the plate heat exchanger (1) and the
PM controller (2) and enters the supply return (E). The
cold potable water (C) is warmed up according to the
continuous flow principle and is available at the hot
water supply of the dwelling (A).
5
2
4
1
3
8
7
10
9
11
Illustr. 5.2 Construction with variable temperature
circuit
10 Strainer (with draining facility) heating circuit
return
11 Strainer (with draining facility) heating water
supply
12 Deaeration potable water circuit
13 Check valve
14 High-efficiency pump
15 Angle pattern valve
with thermostat
16 Contact sensor
Heating operation:
Heating water enters the supply of the heating circuit
of the dwelling (F) via the supply of the heating system
(D). The proportional flow controller (2) opens the path
between the return of the heating circuit (G) and the
supply return (E).
The flow temperature of the heating circuit is conti-
nuously controlled by the contact sensor (16) and the
flow volume of the hot fluid is adjusted by the angle
pattern valve (15). Depending on the setting of the
angle pattern valve (15), cold water from the return of
the heating circuit (G) is added to the heating circuit
supply (F) via the check valve (13) (mixing function).
Heating of potable water:
The proportional flow controller (2) switches to potable
water priority function, if hot water is demanded in
the dwelling. The heating water of the supply (D) passes
across the plate heat exchanger (1) and the PM
controller (2) and enters the supply return (E). The
cold potable water (C) is warmed up according to the
continuous flow principle and is available at the hot
water supply of the dwelling (A).
12
6
only in
variable
temperature
circuit
5
4
13
14
15
7
16
10
11