CSA Intrinsic Safety Installation Drawing.
6335D transmitters are approved as intrinsically safe in Zone 0 Group IIC or Class
I,Division1,Group A,B,C,D when installed according to Installation Drawing.
1. Connections with separate power supply and receiver.
Output: Standard 4 - 20mA loop
Warning:
Substitution of components may impair intrinsic safety.
Channel 1 and Channel 2 are separate channels and therefore separate shielded cables
shall be used for each channel.
The 6335 must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC).
21-12-2000
6335QC02
68
2. Connection with power supply and barrier built into receiver.
Output: Standard 4 - 20mA loop
Warning:
Substitution of components may impair intrinsic safety.
Channel 1 and Channel 2 are separate channels and therefore separate shielded cables
shall be used for each channel.
The 6335 must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC).
1/2
21-12-2000
6335QC02
2/2
69