Cable resistance per wire (max.) ................. 5 Ω
Sensor current ............................................. Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire) .................................................. < 0.002 Ω / Ω
Sensor error detection ................................ Yes
Short circuit detection ................................. If 0% > 30 Ω
TC inputs:
Min.
Max.
Type
temperature
temperature
B
+400°C
+1820°C
E
-100°C
+1000°C
J
-100°C
+1200°C
K
-180°C
+1372°C
L
-100°C
+900°C
N
-180°C
+1300°C
R
-50°C
+1760°C
S
-50°C
+1760°C
T
-200°C
+400°C
U
-200°C
+600°C
W3
0°C
+2300°C
W5
0°C
+2300°C
Cold junction compensation ....................... < ±1.0°C
External CJC with Ni100 or Pt100 .............. -40 ≤ T amb. ≤ 135°C
Sensor error detection ................................ Yes
Sensor error current:
When detecting .................................... Nom. 33 µA
Else ...................................................... 0 µA
Short circuit detection ................................. If 0% > 5 mV
Voltage inputs:
Measurement range ................................... -800...+800 mV
Min. span ..................................................... 2.5 mV
Input resistance ........................................... 10 MΩ
Current output:
Signal range ................................................ 4...20 mA
Min. signal range ......................................... 16 mA
Updating time .............................................. 440 ms
Fixed output signal ...................................... Between 4 and 20 mA
Output signal at EEprom error .................... ≤ 3.5 mA
Load resistance ........................................... ≤ (V
Load stability ............................................... < ±0.01% of span / 100 Ω
24
Min.
span
Norm
100°C
IEC584
50°C
IEC584
50°C
IEC584
50°C
IEC584
50°C
DIN 43710
50°C
IEC584
100°C
IEC584
100°C
IEC584
50°C
IEC584
50°C
DIN 43710
100°C
ASTM E988-90
100°C
ASTM E988-90
(660 ms for diff.)
- 8) / 0.023 [Ω ]
supply
Sensor error detection:
Programmable ............................................. 3.5...23 mA
NAMUR NE43 Upscale ............................... 23 mA
NAMUR NE43 Downscale ........................... 3.5 mA
Ex / I.S. data:
Output, terminal 11...14, (21...24):
U
................................................................. : 28 VDC
i
I
................................................................... : 120 mADC
i
P
................................................................. : 0.84 W
i
L
.................................................................. : 10 µH
i
C
................................................................. : 1.0 nF
i
Input, terminal 41...44, (51...54):
U
................................................................ : 9.6 VDC
o
I
.................................................................. : 28 mADC
o
P
................................................................ : 67.2 mW
o
L
................................................................. : 35 mH
o
C
................................................................ : 3.5 µF
o
EEx / I.S. approval:
DEMKO 99ATEX126961 ..............................
Max. amb. temperature for T1...T6 ............. 60°C
ATEX, applicable in zone ............................. 0, 1 or 2
FM, applicable in ......................................... IS, Class I, Div. 1, Group A, B, C, D
Entity, FM Installation Drawing No. ............. 6335QF01
CSA, applicable in ....................................... IS, Class I, Div. 1, Group A, B, C, D,
Installation Drawing No. .............................. 6335QC02
GOST R approval:
Standard: VNIIM .......................................... Cert. no. Ross DK.ME48.V01899
Ex: VNIIFTRI ................................................ Cert. no. Ross DK.GB06.V00100
Observed authority requirements:
EMC 2004/108/EC
Emission and immunity ....................... EN 61326
ATEX 94/9/EC .............................................. EN 50014 and EN 50020
FM, ASCN ................................................... 3600, 3611, 3610
CSA, CAN / CSA ......................................... C22.2 No. 157, E60079-11, UL 913
Of span = Of the presently selected range
II 1 G
EEx ia IIC T1...T6
IS, Class I, Zone 0, AEx ia IIC
Ex ia IIC
IS, Class I, Zone 0, AEx ia IIC
Standard:
25