Actuators K-175, L-225 - Burkert 2000 Instructions De Montage

Masquer les pouces Voir aussi pour 2000:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 2000, 2002, 2012
2030, 2031, 2032, 2033
Option: Electrical position repeater
10.3.
actuators K-175, l-225
Actuator
Fig. 16: Actuators K-175, L-225 with electrical position repeater
WArnIng!
risk of injury and functional failure due to derailed or slipped
parts!
The actuators contain pre-tensioned springs that may derail or slip
on improper opening.
Actuators K-175 and L-225 shall only be opened in our factory
or by the responsible distributor.
All manuals and user guides at all-guides.com
Parts required
1 Electrical position repeater
with appliance socket
2 Adapter
3 Spindle cap
10.3.1.
Work to be carried out before
installation
DAnger!
hazard due to high pressure!
Interrupt the control air and fluid infeed before modifying the
devices and reduce the pressure in the fluid system.
Interrupt supply of medium
Empty valve housing.
Bring actuator into the upper piston position.
DAnger!
for control function a and I:
risk due to high pressure when screwing on the visibility
hood!
The visibility hood must not be pressurized during attachment.
Therefore pressurize only the lower piston area via the lower
control air connector using compressed air.
Unscrew transparent cap from actuator cover.
Screw off position indicator (yellow screw cap) by hand
③ of the position indicator onto the end of
Screw spindle cap
the spindle (WAF14).
Then interrupt supply of control air.
english