Safety ribbon input
This menu allows the enabling of the safety ribbons and the setting of
their operation logic (see paragraph "Installation").
no
Input disabled (ignored by the control unit).
No jumper with the common is required.
Fot.i
Input enabled for the additional photocells active during
opening and closing
StAn
input enabled for standard safety ribbons with n.c. contact
rESi
input enabled for conductive rubber safety ribbons
with nominal resistance 8,2 kohm.
After having selected the type of safety edge, it is necessary to indicate
the phase of the cycle in which it must be enabled:
AP.Ch
Input enabled in opening and closing phase
AP
Input enabled only in opening phase
Ch
Input enabled only in closing phase
End of Stroke Inputs
City4 control unit allows connecting 2 mechanical ends of stroke
(normally closed contacts) which are activated by the door motion and
showing to the control unit that each door reached its position of
complete opening or closing.
no
end of stroke inputs are disabled
StoP
inputs enabled: the gate stops near the limit switches
rALL
inputs enabled: the gate starts the slowdown phase (menu
t.rAL) near the limit switches.
Enabling the ADI device
This menu makes it possible to enable operation of the device
connected to the ADI connector.
no
interface disabled, any signals will be ignored
Si
interface enabled
*
PLEASE NOTE: selecting Si and pressing MENU accesses the
configuration menu for the device connected to the ADI connector.
This menu is managed by the device itself and is different for each
device. Please refer to the manual for the device.
If the Si option is selected, but no device is connected, the display will
show a series of dotted lines.
Exiting the ADI device configuration menu returns to the i.ADi option
37