Lockouts
46
All manuals and user guides at all-guides.com
ERR.
DESCRIPTION OF ERROR
CODE
Gas pressure switch safety shut-
132
down
Safety time for establishment of
133
flame exceeded
151
BMU fault internal
152
Parameterization error
153
Unit manually locked
160
Fan speed threshold not reached
162
APS does not close
164
Flow/pressure switch HC fault
166
Air pressure switch does not open Air pressure switch does not open
183
Unit in parameterization mode
322
Water pressure 3 too high
323
Water pressure 3 too low
324
Same sensor Input BX
330
Sensor input BX1 no function
331
Sensor input BX2 no function
332
Sensor input BX3 no function
353
Cascade flow sensor B10 missing
384
Extraneous light
385
Mains undervoltage
386
Fan speed tolerance
388
DHW sensor no function
426
Check flue gas damper
427
Config flue gas damper
432
Function ground missing
CAUSE
Interlock, input interrupted
Gas pressure switch is open
Repetition error counter exceeded
Safety time for establishment of fla-
me exceeded
False polarity of the 230V power sup-
ply
Reprogram PCB
Reset button pressed too long
Fan speed threshold not reached
Air pressure switch does not close
Air pressure switch failure
Unit in parameterization mode (para-
meter stick)
Water pressure on input H3 too high
Water pressure on input H3 too low
Same sensor Input BX
Sensor input BX1 no function
Sensor input BX2 no function
Flue gas sensor not programmed cor-
rectly
Cascade flow sensor B10 missing
Short circuit ionization electrode
Mains undervoltage
Fan speed tolerance exceeded
configuration error sensor input B3/
B38
malfunction of flue gas damper
Parameterization flue gas damper
Missing earth connection