Installation
Air/Flue gas system
Requirements and regulations
Regulations for the construction of flue
gas systems are very different for each
country. It should be ensured that all
national regulations with regard to flue
gas systems are respected.
Pay attention to the following recom-
mendations when dimensioning a flue
gas system.
Only approved flue gas material may
be used.
The flue gas system must be properly
calculated to ensure a safe functioning
of the system.
FLUE GAS DATA
Boiler
Nominal heat
type
output
kW
TRIGON
XL
max
min
150
142.3
31.3
200
190.4
42.0
250
237.6
47.0
300
285.7
56.5
400
381.3
79.6
500
476.7
94.6
570
540.2 120.0 550.0 122.2
115
113.7
31.3
350
343.5
75.2
The above table shows the maximum permissible flue resistance were the boiler is still working within specifications.
Nominal heat input -5%.
All manuals and user guides at all-guides.com
Flue gas system components should be
removable for maintenance purposes.
The installer is responsible to apply the
correct diameter, length and type of
flue gas system. If any questions arise
during the calculation contact your lo-
cal manufacturer office for more infor-
mation.
Flue
Nominal heat
gas
input
connection
kW
mm
max
min
145.0
32.2
150 ± 1
194.0
43.1
150 ± 1
242.0
48.4
200 ± 1
291.0
58.2
200 ± 1
388.0
80.5
250 ± 1
485.0
97.0
250 ± 1
250 ± 1
115.8
32.2
150 ± 1
349.0
77.6
250 ± 1
CO
Flue gas
2
Level
temperature
%
°C
max
min
max
min
10.2
9.4
75
60
± 0.2
± 0.2
± 2
± 2
Max
Flue gas
permissible
quantity
flue
resistance
g/s
Pa
max
min
max
min
53.7
12.8
200
10
71.9
17.1
200
10
89.6
19.2
200
10
107.8
23.0
160
10
143.7
30.7
400
10
179.7
38.4
300
10
203.7
48.4
480
10
53.7
12.8
200
10
143.7
30.7
400
10
21
EN