Angle Connector; Boiler Guard - meibes Victaulic 66457.0 Documentation Technique Pour Le Montage Et La Mise En Service

Systèmes pour des grandes installations
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Distributors
4.3 Angle connection
With the angle connection, the boilers, boiler guard and / or distributors are connected at right angles. These are supplied in pairs
and are completely insulated. The matching Victaulic clamps (1 pair) with insulation are also included in delivery.
Art. no.
66457.130
66457.330
66457.730

5. Boiler guard

The boiler guard (see „boiler guard" technical information) can be connected directly to the distributor, or the angle connection depending on
the size and/or pumped quantity. For this, reduction couplings are offered. This way, the distribution system can be put together as needed.
Housing: welded round container with adapter props made from a seamless steel tube incl. a Victaulic groove. In the base there is an opening
for cleaning is with a 1" drain valve. The four 3/4 „sleeves in the ground are used to pick up magnetite separators, which are sealed with
plugs, if none are needed. An automatic fl oating vent, a rinsing ball cock and a pocket immersion sleeve for accommodating the temperature
sensor are located in the lid. The boiler guard is supported by an adjustable foot. Supplied with EPS - block insulation.
Max. permissible pressure rating:
Max. permissible temperaturer:
Effiziente Energietechnik
Ø pipe (AD)
Axis-Centre distance
in mm
(distributor)
114,3
225
168,3
340
219,1
450
a
b
PN 6
110 °C
a in mm
b in mm
275
470
300
500
300
500