4. Distributors

The distributors consist of two stacked chambers with thermal separation of the supply and return lines. The boiler circuit is both connectable
on the left and right hand side. All connections are prepared so that Victaulic clamps can be used. The top outlets for connecting the heating
circuits are designed with Victaulic groove in the nominal width DN 50 (Ø 60.3 mm). All distributors are painted, pressure tested, fully insula-
ted and supplied with two height adjustable feet. Furthermore, 2 Victaulic couplings and 2 end caps are supplied with a 1/2" drill hole as well
as insulation for the Victaulic clamps.
The holes are sealed with plugs. Alternatively, a KFE-cock can be screwed on for emptying. The distributor system consists of elements for
two or three heating circuits, which can be combined as desired, depending on the axis-centre distance.
max. permissible pressure rating:
max. permissible temperature:
4.1 Distributors for 2 heating circuits
Pump volume
Art. no.
up to
66457.0
12 m
/h
3
66457.2
30 m
/h
3
66457.4
50 m
/h
3
66457.6
100 m
/h
3
* at ΔT = 20 K
Effiziente Energietechnik
PN 10
110 °C
Power output
Ø pipe (AD)
up to*
in mm
280 kW
114,3
700 kW
168,3
1150 kW
168,3
2300 kW
219,1
Installation length 1135 mm
250 mm
Height (H) for
H (min.)
a in mm
in mm
guide in mm
170
580
230
760
230
850
230
850
Axis –Centre
the boiler
distance
(AA) in mm
680
225
860
340
1005
450
1005
450