Télécharger Imprimer la page

Sovelor GA/N45C Manuel D'utilisation Et De Maintenance page 30

Publicité

Les langues disponibles

Les langues disponibles

5.4. PREPARATION OF THE GAS BURNER
The space heater is set up in the factory by the manufacturer for one of the operating categories in Table I or Table
II. An adhesive label applied to the gas valve casing will indicate this operating category and the supply pressure for
which the burner has been prepared and tested: that is to say the type of diffuser ring (3) and the gas valve adjustment.
Before starting up the space heater, make sure that the category chosen for the installation is the same as the category
that was set up (paragraph 4.3).
Warning
If the gas category is not the same as the one already set up, carry out the operations described in the
paragraph "Conversion to another type of gas" before starting the heater.
You can continue and start the heater only after it has been set-up according to the instructions for the work category
to be used.
5.5. CONVERSION TO ANOTHER TYPE OF GAS
If the gas category does not correspond to what has already been set up on the space heater and what is indicated
on the adhesive label applied to the machine, perform the operations below, carefully following the sequence indicated:
1) Replace the diffuser ring. Check which type of diffuser ring is indicated for the new category required in Table I or
Table II. If it is different from the one fitted, the diffuser ring is to be replaced as follows:
a. Remove the upper shell of the heater.
b. Unscrew and remove the ionization electrode (5).
c. Unscrew the screws that attach the burner (2) to the combustion chamber (1).
d. Remove the three screws on the burner head plate (2) and change the diffuser ring (3) and then secure it so that
the ignition electrode is equidistant between two successive holes.
e. Reassemble the burner on the combustion chamber and correctly reposition the ionization electrode.
2) Calibrating the gas pressure switch. Check the gas supply pressure value indicated for the new required category
in Table I or Table II and then adjust the gas pressure switch (16) to a value that is 75% of the supply pressure.
3) Adjustment of the gas valve. Check the burner pressure value indicated in Table I or Table II for the new required
category and change the setting on the gas valve during the FIRST START phase (paragraph 4.6).
5.6. FIRST START-UP
Only once you have verified that the space heater is correctly set up for the gas category required for connection,
can you proceed with the first start-up.
First carry out the following operations once again:
• Bleed the gas supply pipe.
• Check that the gas pipe is sealed.
• Open the gas stopcock (10) and check the seal of all connections to the heater.
L-L 304.00-BM
EN
64 / 116

Publicité

loading