11
9
10
11
9
10
Parts (9), (10) and (11) are available as accessories and are not supplied with the heater.
Warning
Only for the 45 kW model
Before connecting the heater to the gas supply line, the gas connection fitting (supplied with the space heater)
must be tightened using special sealant approved for gas installations (sealant not supplied with the heater):
When the line has been connected:
• Bleed the gas supply pipe;
• Check that the gas pipe is sealed.
• Open the gas stopcock (10) and check the seal of all connections to the heater.
Warning
The space heater is set for a maximum supply pressure of 60 mbar.
CHECK THAT THE GAS SUPPLY PRESSURE IS NEVER MORE THAN 60 mbar.
If the supply pressure exceeds this value, the gas valve safety membrane may rupture and put the valve into a
permanent safety block (in this case the valve, which cannot be repaired, must be replaced).
L-L 304.00-BM
EN
8
8: space heater
9: low pressure flexible gas tubing
10: stopcock
11: Filter – Gas regulator
8
8: space heater
9: medium pressure flexible gas tubing
10: stopcock
11: Filter – Gas regulator