Warnings!
Motor Overload Protection
ƒ
For information on the protection level of the internal overload
–
protection for a motor load, see the corresponding manuals or
software helps.
If the integral solid state motor overload protection is not used,
–
external or remote overload protection must be provided.
Branch Circuit Protection
ƒ
The integral solid state protection does not provide branch circuit
–
protection.
Branch circuit protection has to be provided externally in accordance
–
with corresponding instructions, the National Electrical Code and any
additional codes.
If mounted on a motor the environmental rating tests for Type 4 and
ƒ
Type 12 shall be performed.
Fuses/circuit breakers
ƒ
See this manual for maximum fuse/circuit breaker sizes and circuit
–
breaker types.
Voltage rating of the fuses and circuit breakers must at least be
–
suitable for the input voltage.
E82MV251_2B ... E82MV371_2B (0.25 kW ... 0.37 kW, 240 V devices):
ƒ
Suitable for use on a circuit capable of delivering not more than
–
5000 rms symmetrical amperes, 240 V maximum, when protected by
fuses or circuit breakers.
Suitable for use on a circuit capable of delivering not more than
–
50000 rms symmetrical amperes, 240 V maximum, when protected by
CC, J, T or R class fuses.
Maximum surrounding air temperature: 0 ... +60 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
–
E82MV551_4B ... E82MV752_4B (0.55 kW ... 7.5 kW, 400/500 V devices):
ƒ
Suitable for use on a circuit capable of delivering not more than
–
5000 rms symmetrical amperes, 500 V maximum, when protected by
fuses or circuit breakers.
Circuit breakers only for use in WYE 480/277V source.
–
Suitable for use on a circuit capable of delivering not more than
–
50000 rms symmetrical amperes, 500 V maximum, when protected by
CC, J, T or R class fuses.
Maximum surrounding air temperature: 0 ... +60 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
–
8
EDK82MV752-BB DE/EN/FR 2.1