4.11 BURNER START-UP PROGRAM DIAGNOSTIC
During start-up, indications are explained in the following table:
Sequences
Preventilation
Ignition phase
Operation with flame ok
Operation with weak flame
Electrical supply lower than
Lock-out
Extraneous light
Key:
Key
4.12 OPERATING FAULT DIAGNOSTICS
The control box has a self-diagnostic system, which easily allows identifying the operating faults (RED LED
signal).
ITo use this function, wait at least ten seconds from the safety lock out, and then press the reset button for
a minimum of 3 seconds.
After releasing the button, the RED LED starts flashing as shown in the diagram below.
RED LED on
wait at least 10 s
The pulses of the LED constitute a signal with intervals of approximately three seconds.
The number of pulses will provide the information on the possible faults, according to the table below:
SIGNAL
2 blinks
3 blinks
4 blinks
7 blinks
8 blinks
10 blinks
5840
COLOUR CODE TABLE
~
170V
Yellow
Press button
for > 3 secs
No stable flame is indicated in the safety period:
– faulty photocell;
– oil valve fault;
– faulty ignition transformer;
– poor burner regulation.
– Not used.
– Light in the chamber before ignition.
Loss of flame during operation:
– poor burner regulation;
– oil valve fault.
– Faulty thermostat for oil enabling signal;
– Heating resistors blown.
– Wiring error or internal fault;
– Presence of electromagnetic disturbance: use the radio disturbance protection
kit.
Green
Red
Interval
signal
3 secs
PROBABLE CAUSE
13 GB