Télécharger Imprimer la page

Maintenance; Troubleshooting - AERMEC OMNIA HL Manuel D'utilisation Et D'installation

Ventilo-convecteur

Publicité

Les langues disponibles
  • FR

Les langues disponibles

MAINTENANCE

ROUTINE MAINTENANCE
Routine maintenance can be carried
out by the user: it involves a series
of simple operations, thanks to
which the fan coil can operate at its
maximum efficiency level.
Interventions:
- External cleaning, weekly to be car-
ried out with a moist cloth and
neutral soap; do not use other
detergents and solvents of any
type.
- Cleaning the electrostatically pre-
charged filter, every two weeks
or weekly if the installation is in a
very dusty environment, remove
the dust that has accumulated
with a vacuuming device, wash-
ing with running water and neu-
tral soap is allowed but it speeds
up the deterioration of the elec-
trostatic precharge; do not use
other detergents and solvents of
any type.
- Replacement of the electrostatically
precharged filter every two years.
Failure to make this replacement
in the time specified means the
end of the filtering of the micro-

TROUBLESHOOTING

PROBLEM
Insufficient air flow at
outlet
Unit does not heat
Unit does not cool
Fan not turning
Condensation forming
on the external case of
the unit
For any problems not listed, contact the After Sales Service immediately.
dusts because the electrostatic
precharge has run out; the filter-
ing capacity will be compared
with that of a normal filter.
- Visual inspection of the state of the
fan coil for every maintenance
operation; every fault must be
communicated to the After Sales
Service department.
EXTRAORDINARY MAINTENANCE
Extraordinary maintenance can only
be performed by Aermec After-
Sales Services or by people with
the technical and professional req-
uisites qualifying them to under-
take installation, conversion,
expansion and maintenance of
the systems and are able to check
them in terms of safety and func-
tionality, in particular with regard
to electrical connections the fol-
lowing tests are required relative
to:
- Measurement of the electrical sys-
tem insulation resistance;
- Continuity of the protection wires
Extraordinary maintenance consists
of a set of complex operations that
PROBABLE CAUSE
Incorrect speed setting on control panel
Blocked filter
Obstructed air flow (inlet and/or outlet)
No hot water
Incorrect control panel setting
No cold water
Incorrect control panel setting
No electrical power
Water has not reached operating temperature.
Temperature and humidity limits specified by
"MINIMUM AVERAGE WATER TEMPERATURE" have
been reached
involve the dismantling of the fan
coil or its components, resulting
in the restoration of the fan coil's
functioning at maximum efficiency.
Interventions:
- Internal cleaning, annually or before
shutting down for long periods;
cleaning can be more frequent
in environments where a high
degree of air cleaning is required;
it consists of cleaning the coil, the
removable volute, the fan fins, the
basin and all the parts in contact
with the treated air.
- Repairs and fine tuning: if you
notice anomalies, consult the
"TROUBLESHOOTING" charter of
this manual before contacting the
After Sales Service.
SOLUTION
Select the correct speed on the control panel
Clean the filter
Remove the obstacle
Check the boiler
Set the control panel
Check the chiller
Set the control panel
Check that there is electrical power
Check heater or chiller.
Check thermostat setting
Raise the water temperature above the
limits specified by "MINIMUM AVERAGE
WATER TEMPERATURE"

Publicité

Chapitres

loading

Ce manuel est également adapté pour:

Omnia hl mOmnia hl 11 omnia hl 16Omnia hl 26Omnia hl 36Omnia hl 11 mOmnia hl 16 m ... Afficher tout