THE SAUNA ROOM SHALL BE PROVIDED WITH PROPER VENTILATION
Note: Control panel and power unit must be installed in a dry
place; away from spa, pool or shower; not outdoors. A
receptacle shall not be installed inside the sauna room.
Note (only in Canada): Sauna heaters shall not be
subjected to water spray. Shower heads shall not be
installed above the sauna heaters!
Load Center
Load center shall be supplied by
electrical contractor during field
wiring, and shall be 2 pole 2
breaker subpanel model. Load
center can be located in other
serviceable places, as well as
location shown on this diagram.
All the wiring to the sauna
heater and accessories shall
be routed away from any
direct radiation from the
sauna heater.
Figure 1. Digital Sauna Control CG170-U1, CG170-U3, CX170-U1 and CX170-U3
INSTALLATION OF WALL MODEL HEATER,
CONTROL, CONTACTOR
1. Remove heater from carton and attach heater
to wall with screws are supplied. If wall thickness
is less than 3/4" (19 mm), use 2"x 4" (50 x 100 mm)
backing behind heater. Observe proper clearances
as per page 3 and table 1.
2. See applicable wiring diagram fig. 5–6 for
heater model. Heater must be permanently
installed (no pigtails or plug allowed) and wiring
must be done by a licensed electrician, who must
follow wiring diagram provided and adhere to local
codes. Use proper A.W.G. rated wire size and use
copper wire suitable for 194°F (90°C) within Sauna
walls. Use grounding terminals provided in Sauna
heater, control system, and contactor to properly
ground the equipment as per NEC and local codes.
3. Inside the heater box there are two signs.
Please place the metal "CAUTION" sign on the
interior wall of the Sauna room directly above
the heater in a visible place. Place the metal
"WARNING" sign outside, on the door of the
Sauna room. "MAINTENANCE INSTRUCTIONS"
are at the end of this manual.
Control Panel
Power Unit
WIRE ROOM LIGHT
DE LA CABINE #14 AWG 194°F/ 90°C
4"/
100mm
Sensor
Room Light
INSTALL HEATER WITH #6-2"/
152-50mm SHEET METAL SCREWS
HIGH LIMIT
7" to
SWITCH
12"
FLEX METAL CONDUIT
194°F/90°C WIRE
NOTE:
CONTROL AND
CONTACTOR
MUST BE
INSTALLED IN A
DRY PLACE AWAY
FROM SPA, POOL,
SHOWER, AND
NOT OUTDOORS.
178 to
305 mm
3