When an existing Category 1 heater is removed or replaced, the
original venting system may no longer be sized to properly vent the
attached appliances. Instructions shall also indicate effects of an
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system are
not in operation:
1.
Seal any unused openings in the venting system.
2.
Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or the Natural Gas and Propane Installation
Code, CSA B149.1 and these instructions. Determine that
there is no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe condition.
3.
As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
Model
Input BTU/HR (KW/H)
Height
Width
Depth
Gas Inlet (Pipe)
Blower Kit
Description
Vinyl Siding Vent Kit
Vinyl Siding Vent Kit
Model Number
DV984
DV983
Part Number
17085
17084
17087
17086
37408-8-1020
INTRODUCTION (CONT'D)

SPECIFICATIONS

DV-25
25,000 (7.3)
Natural
28" (711mm)
37" (940mm)
11 1/2" (292mm)
1/2" (13mm)
Accessories for the Above Furnaces
DRB-1
VINYL SIDING VENT KITS
DV-822
VSK-2
VENT EXTENSION KITS
Description
Vent Extension Kit For Propane
Units (13"-19" Walls)
Vent Extension Kit For Propane
Units (13"-19" Walls)
CONVERSION KITS
Description
Propane to Natural
Natural to Propane
Propane to Natural
Natural to Propane
improperly sized venting system (formation of condensate, leakage,
spillage, etc.) and shall specify the following test procedure:
4.
Close fireplace dampers.
5.
Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating
at maximum speed. Do operate a summer exhaust fan.
6.
Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7.
Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8.
If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance
with National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or
Natural Gas and Propane Installation Code, CSA B149.1.
9.
After is has been determined that each appliance connected
to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace
dampers and any other gas-fired burning appliance to their
previous conditions of use.
24,000 (7.0)
Propane
Model Number
DV-35
35,000 (10.3)
28" (711mm)
37" (940mm)
11 1/2" (292mm)
1/2" (13mm)
DRB-1
DV-822
VSK-2
Used On
DV35-4SGLPG
DV35-4SGNAT
Used On
DV25-5SGLPG
DV25-5SGNAT
DV35-4SGLPG
DV35-4SGNAT
Page 7