Notes
Remote potentiometer
With the variant MK 9962N.82/300 the time setting can also be made
via remote potentiometer of 10 kOhms. It is connected to the terminals
Z1-Z2. The corresponding potentiometer on the relay has to be set to min. If
no remote potentiometer is required the terminals Z1-Z2 have to be linked.
The wires to the remote potentiometers should be installed separately
from the lines with mains voltage. If this is not possible, a screened cable
is recommendet where the shield is connected to Z2.
To terminals Z1 and Z2 no external voltage must be connected, as the unit
might be damaged.
Control input B1
The unit needs a continuously connected auxiliary supply on A1-A2. The
timing is controlled via input B1. The control unit B1 (+ with DC) has to be
supplied with voltage against A2. The control signal could be the same as
the auxiliary/control voltage of A1 or any other voltage between 12 and
240 V AC or DC. Operating a parallel load (e.g. a contactor) between B1
and A2 is also allowed.
Time interruption and time addition with X2 - X3
The time delay can be interrupted during timing by bridging the terminals
X2 - X3. By opening the bridge the time continues (time addition).
While X2 and X3 are bridged the control input is disabled and the yellow LED
remains in the state it had at stop. No external voltage must be connected
to X2 and X3 as the unit may be damaged.
Setting
Green LED
on when voltage
connected
Yellow LED "R/t"
shows state of contacts
and timing
(see also indicators)
Time range selector switch
Time setting
M8285_b
Technical Data
Time circuit
Time ranges:
Time setting:
Setting accurancy:
Minimum on time (B1):
AC 50 Hz:
DC:
Repeat accuracy:
Voltage and
temperature influence:
Input
Auxiliary voltage U
:
H
Voltage range:
Frequency range (AC):
Nominal consumption
at AC 12 V:
at AC 24 V:
at AC 240 V:
at DC 12 V:
at DC 24 V:
at DC 240 V:
Release voltage (A1/A2)
AC 50 Hz:
DC:
Control voltage (B1/A2):
Voltage range (B1/A2):
Control current (B1):
Release voltage (B1/A2)
AC 50 Hz:
DC:
Output
Contacts
MK 9962N.82:
Contact material:
Measured nominal voltage:
Thermal current I
:
th
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13:
Electrical life
to AC 15 at 1 A, AC 230 V:
Permissible switching
frequency:
Short circuit strength
max. fuse rating:
Mechanical life:
14
8 time ranges settable via rotational
switch:
0.05 ...
1 s
0.3 ...
0.06 ...
6 s
3 ... 300 min
0.3 ... 30 s
0.3 ...
0.03 ...
3 min
3 ...
Continuous, 1:100 on relative scale
± 10 %
Approx. 15 ms
Approx. 5 ms
± 0.5 % of selected
end of scale value + 20 ms
≤ 1 % with the complete operating range
AC/DC 12 ... 240 V
0.8 ... 1.1 U
N
45 ... 400 Hz
Approx. 1.5 VA
Approx. 2 VA
Approx. 3 VA
Approx. 1 W
Approx. 1 W
Approx. 1 W
Approx. 7.5 V
Approx. 7 V
AC/DC 12 ... 240 V
0.8 ... 1.1 U
N
Approx. 1 mA, over complete voltage
range
Approx. 3.5 V
Approx. 3 V
2 changeover contacts
AgNi
AC 250 V
See quadratic total current limit curve
(max. 4 A per contact)
3 A / AC 230 V
IEC/EN 60947-5-1
1 A / AC 230 V
IEC/EN 60947-5-1
1 A / DC 24 V
IEC/EN 60947-5-1
1.5 x 10
switching cycles
5
6000 switching cycles / h
4 A gG / gL
IEC/EN 60947-5-1
≥ 30 x 10
switching cycles
6
MK 9962N / 08.04.22 en / 550A
30 min
30 h
300 h