4.2. COMPRESSOR
Compressor type is of hermetic Scroll.
The compressor motor, refrigerant gas cooled type, is equipped with automatic reset internal thermal protection.
The compressor is mounted on rubber anti vibration pads.
4.3. EVAPORATOR
Evaporator is provides by the installer. Its capacity must correspond to that of condensing unit for the correct
operation of installation.
4.4. AIR COOLED CONDENSERS
Condenser coils consist of seamless copper tubes arranged in a staggered row pattern. Each coil is mechanically
expanded into aluminium fins with full fin collars.
4.5. CONDENSEUR FAN AND MOTOR
The fan type is of the direct drive Helicoidal. The motor is equipped with an internal heat overload protection with
an automatic reset function. The rotational speed of the fan or fans is managed by a condensing pressure regulator
allowing for operation at low outdoor temperatures (refer to Operating Limits).
4.6. ELECTRICAL PANEL
All electrical equipment required for proper unit operation is located in a weatherproof electrical panel with access
on the front of the unit.
The CE compliance of electrical panel is assured by an access panel fixed by bolts. The electrical panel has a main
switch with externally lockable handle, power contactors, compressor thermal overload, control circuit fuses, high
pressure cut-out, antishort cycle time delay and electrical junction blocks for power and control circuits. Indoor
unit regulation is not supplied
5. CONTENTS OF PACKAGE
1
SYSAQUAC
1
Bag with the documentation
5.1. OPTIONALS ACCESSORIES
Anti-vibration rubber pads
Spring pads
On opening the carton, check that all the accessories required for installation are present.
6