Examples
• One external level sensor.
– emptying function.
L
• One external level sensor.
– filling function.
L
Fig. 32 Constant level
11.4.7 Constant other value
Any other value is kept constant.
11.4.8 Constant curve
The pump can be set to operate according to a constant curve,
like an uncontrolled pump. See fig. 33.
The desired speed can be set in % of maximum speed in the
range from 25 to 100 % (110 %).
H
Fig. 33 Constant curve
20
11.5 Analog inputs
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
Analog input 1, setup (4)
Analog input 2, setup (7)
Analog input 3, setup (14)
To set up an analog input, make the settings below.
Function
The analog inputs can be set to these functions:
Not active
•
Feedback sensor
•
Ext. setpoint infl.
•
See section 11.13
Other function.
•
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system by the sensor connected to the actual analog input.
Unit
Available measuring units:
Parameter
Pressure
Pump flow
Liquid temp.
Other parameter
Electrical signal
Select signal type (0.5 - 3.5 V, 0-5 V, 0-10 V, 0-20 mA or
4-20 mA).
Sensor range, min. value
Set the min. value of the connected sensor.
Sensor range, max. value
Set the max. value of the connected sensor.
11.6 Pt100/1000 inputs
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
Q
Pt100/1000 input 1, setup (17 and 18)
Pt100/1000 input 2, setup (18 and 19)
Function
The Pt100/1000 inputs can be set to these functions:
Not active
•
Feedback sensor
•
Ext. setpoint infl.
•
See section 11.13
Other function.
•
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system.
FM 300
(advanced)
●
●
●
Setpoint influence
.
Possible units
bar, m, kPa, psi, ft
3
3
m
/h, l/s, yd
/h, gpm
°C, °F
%
FM 300
(advanced)
Setpoint influence
.
●
●