6.0 FINISHING
EN
VENTILATION OPENINGS ARE REQUIRED IN ENCLOSURES UP TO 96" HIGH. THEY ARE
RECOMMENDED FOR ALL ENCLOSURES. ABOVE 84" COMBUSTIBLE FINISHING MATERIALS MAY
USE ONLY A NON-COMBUSTIBLE MATERIAL TO FINISH THE FACE OF THE APPLIANCE. A NON-
COMBUSTIBLE MATERIAL SUCH AS CEMENT BOARD IS REQUIRED FOR THIS PURPOSE.
The appliance is shipped with a template that is 1/8" (3.2mm) larger on the
top, bottom and each side than the faceplate. Leave the template in place
when installing the fi nishing material to insure the faceplate will fi t inside the
fi nishing material edging..
NOTE: A ventilated enclosure
is recommended. See
"VENTILATION OPENINGS"
section.
DRYWALL
NOTE: JOINT
COMPOUNDS AND
TAPES THAT ARE
RESILIENT TO HEAT
AND CRACKING
SHOULD BE USED
WHEN TAPING AND
MUDDING SEAMS.
W415-0711 / D / 05.09.13
BE USED ON THE FRONT FACE.
DO NOT INSULATE AROUND THE APPLIANCE.
7 3/4"
(196.8MM)
MIN
40"
55 1/2"
(1016MM)
(1409.7MM)
EMBER STRIP
7 3/4" (196.8MM) MIN CEMENT
THE UNIT TO COMBUSTIBLES
WARNING
!
TEMPLATE
NON-COMBUSTIBLE
MATERIAL
BOARD FROM THE SIDE OF
FACE MUST
HAVE A
MINIMUM
84"(2133.6MM)
HEIGHT OF
CEMENT BOARD
DEPENDING
UPON CEILING
HEIGHT
COMBUSTIBLE
FACING AND
WOOD FRAMING
MAY START AT
84"(2133.6MM)
ABOVE THE
BASE OF THE
UNIT