Limit switch input
The two micro switches installed on the motor may work in three
different modes according to the FC.En parameter settings (for detailed
information please refer to chapter 4).
StoP
Inputs enabled: the door stops by the limit switches.
rALL
Inputs enabled: the door begins the slow-down stage
(t.rAL menu) by the limit switches.
ShAd
Inputs enabled: the "shadow area" function is activated when
the LEFT micro switch trips and disabled when the RIGHT micro
switch trips
no
Inputs disabled (the control unit ignores them).
There is no need to use a jumper with the common.
Motor Release on mechanical stop
When the door halts against the mechanical stop, the motor is
controlled for a fraction of a second in the opposite direction,
decreasing the motor gear tension.
0
Function disabled
1÷10
Time motor release (max. 1 second)
Enabling the ADI device
This menu makes it possible to enable operation of the device
connected to the ADI connector.
no
interface disabled, any signals will be ignored
Si
interface enabled
PLEASE NOTE: selecting Si and pressing MENU accesses the
configuration menu for the device connected to the ADI connector.
This menu is managed by the device itself and is different for each
device. Please refer to the manual for the device.
If the Si option is selected, but no device is connected, the display will
show a series of dotted lines.
Exiting the ADI device configuration menu returns to the i.ADi option
WARNING: before starting the automatic self-teaching
procedure disable this menu.
66