Type 8690 Ex
control function
Process valve closed
a
in rest position
(by spring force)
Process valve open
B
in rest position
(by spring force)
Process valve closed
in rest position
i
Process valve open
in rest position
Tab. 6:
Pneumatic connection to actuator
Installation
pneumatic connection type 8690
with actuator
pilot air outlet
pilot air port
type 8690
actuator
lower pilot air port
2
of the actuator
1
should be con-
nected to the
2
upper pilot air port
2
of the actuator
upper pilot air port
2
of the actuator
1
should be con-
nected to the
2
lower pilot air port
2
of the actuator
lower pilot air port
2
of the actuator
1
upper pilot air port
2
of the actuator
2
upper pilot air port
2
of the actuator
1
lower pilot air port
2
of the actuator
2
7.4.
rotating the actuator module
The actuator module (Pneumatic Control Unit and actuator)
can be rotated for straight seat valves and angle seat valves
only!
The position of the connections can be aligned steplessly by rotating the
actuator module (Pneumatic Control Unit and actuator) through 360°.
Only the entire actuator module can be rotated. The Pneu-
matic Control Unit cannot be rotated contrary to the actuator.
The process valve must be in the open position for alignment
of the actuator module!
DangEr!
risk of injury from high pressure!
• Before dismounting lines and valves, turn off the pressure and
vent the lines.
procedure:
→
Clamp valve body in a holding device (only required if the process
valve has not yet been installed).
→
Control function A: Open process valve.