Clearances
Chase Clearances
Chase Ceiling
The inner top portion of the chase must be covered with non-combustible material (firestop) . No exposed
combustible materials are permitted inside the chase .
Floor Clearance
The minimum clearance required from the bottom of the fireplace to the floor is 3" (8 cm) .
!
NOTE: Install appliance on hard metal, cement board, drywall or wood surfaces, extending full width and depth .
DO NOT install directly on carpeting, vinyl, or any combustible material other than wood .

Additional Clearances

Ceiling Clearance
The minimum ceiling height required for installation of
all models is 96" (2 .4 m) .
The minimum clearance required from the top of the
glass to the ceiling is 40" (1 m) .
The heat release above the fireplace is critical
for keeping the chase and surrounding walls at a
relatively low temperature .
Adjacent Wall Clearance
The minimum distance to any side adjacent wall is 7"
(178 mm) from the glass for all models .
Front Clearance
Do not put furniture or any combustible objects within 36" (0,9 m) of glass front of appliance .
39
WARNING
!
Ceiling
Ceiling
Clearance
Clearance
Min . 40"
Min . 40"
(1 m)
(1 m)
Adjacent Wall
Adjacent Wall
Min . 7" from Glass
Min . 7" from Glass
FaberFires.com