External Control With Intellicomm Communication Center - Pentair STA-RITE INTELLIFLO VSD Serie Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 118
27
External Control with IntelliComm
The IntelliFlo
Center using the RS-485 communications cable. The IntelliComm provides four pairs of input
terminal connections. These inputs are actuated by either 15 - 240 VAC or 15 - 100 VDC. Using
the device's inputs, the programmed IntelliFlo
Note: For the IntelliFlo
in the "Running Schedules" mode (LED above the Start/Stop button lit).
If more than one input is active the highest number will be communicated to the IntelliFlo
pump. The IntelliComm will always communicate to pump using ADDRESS #1.
Program number priority is as follows: Example: If programs 1 and 2 are activated, program
2 will run, regardless of the assigned speed (RPM). The higher program number (2 being
higher) will always take priority. The following table shows the wiring terminal descriptions for
IntelliComm.
External Control
Terminal
Number
1-2
3-4
5-6
7-8
9-10
11
12
pump can be remotely controlled by the Pentair IntelliComm Communication
®
pump to accept commands from IntelliComm, the pump must be
®
IntelliComm Communication Center
Terminal Name
Voltage
Power Supply
100 - 240 VAC
15 -240 VAC
Program 1
or
15 - 100 VDC
15 -240 VAC
Program 2
or
15 - 100 VDC
15 -240 VAC
Program 3
or
15 - 100 VDC
15 -240 VAC
Program 4
or
15 - 100 VDC
RS-485
-5 to +5 VDC
+ Data: Yellow
- Data: Green
Ground
Communication Center
®
pump speeds can be controlled.
®
Maximum
Current
100 mA
1 mA
1 mA
1 mA
1 mA
5 mA
Phase Type
Frequency
1 Input
50/60 Hz
1 Input
50/60 Hz
1 Input
50/60 Hz
1 Input
50/60 Hz
1 Input
50/60 Hz
1 Output
N/A
®

Publicité

Table des Matières
loading

Table des Matières