Functions menu
When programming, the operator needs to be in stop mode.
⚠
F1 Total stop [1-2]
NC input – Gate stop that excludes any automatic closing; to resume movement, use the control device. The safety device is inserted into [1-2];
if unused, select 0.
F2 Input [2-CX]
NC input – For associating: C1 = reopening during closing for photocells, C2 = closing back up during opening for photocells, C3 = partial stop,
C4 = obstruction wait, C7 = do not use, C8 = do not use.
F3 Input [2-CY]
NC input – For associating: C1 = reopening during closing for photocells, C2 = closing back up during opening for photocells, C3 = partial stop,
C4 = obstruction wait, C7 = do not use, C8 = do not use.
F5 Safety test
After every opening or closing command, the board will check whether the photocells are working properly.
F6 Maintained action
The gate opens and closes by keeping the button pressed. Opening button on contact 2-3 and closing button on contact 2-4. All other control
devices, even radio-based ones, are excluded.
F7 Command [2-7]
From the control device connected to 2-7 it performs the step-step (open-close-invert) or sequential (open-stop-close-stop) command.
F8 Command [2-3P]
From the control device connected to 2-3P it executes the pedestrian opening (completely opens the M2 gate leaf) or partial opening (it partially
opens the M2 gate leaf: the opening arc depends on the percentage of travel set up with F36).
F9 Obstruction detection with motor idle
With the gate closed, opened or totally stopped, the gearmotor stays idle if the safety devices, that is, photocells or sensitive safety-edges
detect an obstruction.
F10
Do not modify. Function unavailable.
0= Deactivated / 1 = Activated (default)
0= Deactivated (default) / 1=C1 / 2=C2 / 3=C3 / 4=C4 / 7=C7 / 8=C8
0= Deactivated (default) / 1=C1 / 2=C2 / 3=C3 / 4=C4 / 7=C7 / 8=C8
0= Deactivated (default) / 1=CX / 2=CY / 3=CX+CY
0= Deactivated (default) / 1= Activated
0 =Step-step (default) / 1= Sequential
0 = Pedestrian opening (default) / 1= Partial opening
0= Deactivated (default) / 1= Activated
0= Deactivated (default)