Torque Specifications; Specifications For Grid Protection - SMA SUNNY TRIPOWER 60 Instructions D'installation

Masquer les pouces Voir aussi pour SUNNY TRIPOWER 60:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5  Technical Data

5.5 Torque Specifications

Figure 5.2 Overview of Inverter with Torque Indications
Parameter
1
M63 cable gland
2
Terminals on AC
terminal block
3
Primary PE
(secondary PE to
the immediate
right)
4
Terminals on DC
5
M32 cable gland
6
Swivel nut for M32
cable gland
7
M25 cable gland
8
Swivel nut for M25
cable gland
9
M6 equipment
grounding
(equipotential
bonding terminal)
Front screw (not
shown)
Table 5.7: Torques
If the blind plugs are removed (see (7) in figure 5.2 ), use
the following fittings: 3, 3S, 4, 4X, 6, 6P.
50
STP60-10-IA-xx-10
Tools
Torque
Wrench 65/68
6 Nm (53 in-lbf)
mm
TX 30
14 Nm
(124 in-lbf)
TX 30
3.9 Nm
(35 in-lbf)
TX 30
14 Nm
(124 in-lbf)
Wrench, 36 mm
6 Nm (53 in-lbf)
Wrench, 36 mm
1.8 Nm
(16 in-lbf)
Wrench 33 mm
10 Nm
(89 in-lbf)
Wrench 33 mm
1.8 Nm
(16 in-lbf)
TX 20
3.9 Nm
(35 in-lbf)
TX 30
1.5 Nm
(13 in-lbf)
5.6 Specifications for Grid
Protection
Parameter
Maximum inverter current, I
Recommended blow fuse type gL/gG (IEC
60269-1)
Recommended blow fuse Class T (UL/USA)
Recommended circuit breaker type B or C
Maximum fuse size
Table 5.8: Specifications for grid protection
INFORMATION
Observe local regulations.
SMA Solar Technology AG
Specification
87 A
ACmax
100 to125 A
125 A
125 A
125 A
Installation Guide

Publicité

Table des Matières

Dépannage

loading

Table des Matières