5 Technical Data

5.1 Specifications

Parameter
AC
Nominal apparent power
2)
Nominal active power
1)
Reactive power range
Nominal AC voltage (voltage range)
Supported grounding systems
Nominal AC current
Max. AC current
AC total harmonic distortion (THD at nominal output power)
Inrush current
Maximum residual output current
Power factor – standard
Displacement power factor - regulated
Stand-by power consumption (for communication)
Nominal power frequency (range)
DC
Input voltage range
Nominal DC voltage
MPPT voltage range - nominal power
Max. DC voltage
Min power on the grid
Max. DC MPPT current
Max. DC short-circuit current
MPP tracker/Input per MPPT
Overvoltage categories
Efficiency
Max. efficiency EU/CEC
EU efficiency at 630 V
DC
CEC efficiency at 400/480 V
Installation Guide
1)
4)
4)
AC
STP 60-10
60 kVA
60 kW
0 to 60 kVAr
3P + PE (WYE) / 400-480 V (+/- 10 %)
TT, TN
3 x 87 A
3 x 87 A (3 x 72 A @ 480 V)
< 1%
9.2 A/5 ms
49.8 A RMS over three periods
> 0.99 at nominal power
0.8 overexcited to 0.8 underexcited
3 W
50/60 Hz (+/- 10%)
565 to 1,000 V at 400 Vac
680 to 1000 V at 480 Vac
630 V at 400 Vac
710 V at 480 Vac
570 to 800 V at 400 Vac
685 to 800 V at 480 Vac
1,000V
100 W
110 A
150 A
1/1 (when using an external PV array junction box)
AC: Overvoltage category III (OVC III),
PV: Overvoltage category II (OVC II)
98.8%
98.3%
98.0%/98.5%
5  Technical Data
STP60-10-IA-xx-10
45