Technical Data; Standard Type; Troubleshooting; Maintenance And Repairs - DOLD NE 5021 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data

Switching distances
Safe switching distances
without mounting difference
:
S
an
:
S
ab
undefined situation:
7.1 ... 17.9 mm
San
sensor
actuator
M8351_a
Safe switching distances
with mounting difference
The switching distance S
is valid for mounting method A and B when
an
the switch is mounted on non ferromagnetic material. The min. distance
between transmitter and receiver should be 3 mm. The receiver must not
be used as mechanical stop for the transmitter.
Mounting Difference / Switching Distance S
X2
X1
Y2
NE 5021.22/100
Mounting diff.
S
an
≤ 9 mm
Y
= max. 7 mm
1
≤ 6 mm
Y
= max. 5 mm
2
≤ 6 mm
X
= max. 7 mm
1
≤ 6 mm
X
= max. 7 mm
2
Mounting Difference / Switching Distance S
b2
b1
a2
NE 5021.22/100
Mounting diff.
S
an
≤ 11 mm
a
= max. 5 mm
1
≤ 9 mm
a
= max. 5 mm
2
≤ 8 mm
b
= max. 5 mm
1
≤ 8 mm
b
= max. 5 mm
2
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail: dold-relays@dold.com • internet: http://www.dold.com
≤ 7 mm
≥ 18 mm
Sab
sensor
actuator
Mounting Method A
an
Y1
actuator
S
sensor
M8250_a
Mounting Method B
an
a1
actuator
S
sensor
M8249_a
Technical Data
Output
Contacts:
Contact type:
NO contact
Switching voltage:
Switching current:
Series resistor for contacts:
Electrical life:
NC contact
The NC contact requires an external series resistor R
The connection 32 (pink) must be connected to + U
The connection 31 (grey) has to be connected via a series resistor R
The value of Rv is depending on the applied voltage.
Switching voltage U
B
adjusted by R
and I
:
V
n
U
max:
B
I
typ.:
n
I
max.:
n
General Data
Temperature range:
Operation:
Storage:
Altitude:
Shock resistance:
Vibration resistance:
Protection class:
Housing:
Connection of cable:
Length of cable:
Mounting:
Weight:
Transmitter:
Receiver:
Dimensions
Width x height x depth:
Transmitter:
Receiver:

Standard Type

NE 5021.22/100
Article number:
• Output:
• Connection cable:

Troubleshooting

Failure
LED OFF

Maintenance and repairs

- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356
12
2 NO / 1 NC contacts
Reed contacts
typ. DC 24 V
max. DC 30 V
max. 100 mA
10 Ω
> 2 x 10
switching cycles at
6
DC 24 V / 100 mA
V
B
R
= (U
- 3.3) V
B
V
I
n
DC 30 V
6 mA
10 mA
- 25 ... + 75 °C
- 40 ... + 85 °C
< 2,000 m
30 g / 11 ms
10 g, 10 ... 150 Hz
IP 67
IEC/EN 60 529
Polyamid, glas-fibre reinforced with
V0 behaviour according to UL subj. 94
0.25 mm
with tinned wire ends
2
5 m
Screw M4
with plain washer
EN ISO 7092
45 g
120 g
88 x 14 x 25 mm
88 x 14 x 25 mm
0054697 (for Transmitter and Receiver)
2 NO contacts / 1 NC contact
5 m
Potential cause
- incorrect voltage value is connected
on 32
- incorrect resistance R
is connected
V
on 31
- Distance between transmitter and
receiver to large
NE 5021 / 05.12.18 en / 040A
V

Publicité

Table des Matières
loading