Technical Data

Input
Nominal voltage U
:
N
Voltage range:
at 10% residual ripple:
at 48% residual ripple:
Nominal consumption:
Nominal frequency:
Control current:
Output
Contacts
BN 3081.63:
The NO contacts are safety contacts.
ATTENTION! The NC contacts 81-82 can only be used for monitoring.
Response / release time of
K1 and K2:
Contact type:
Nominal output voltage:
Thermal current I
:
th
Switching capacity
to AC 15
NO contact:
to DC 13
NO contact:
to DC 13
NO contact:
Electrical life
to AC 15 at 2 A, AC 230 V:
Permissible operating
frequency:
Short circuit strength
max. fuse rating:
max. automatic fuse:
Mechanical life:
General Data
Operating mode:
Temperature range
operation:
storage :
altitude:
Clearance and creepage
distances
rated impulse voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Frequency / Amplitude:
Acceleration:
AC 110, 115, 120, 230 V;
DC 110 V
AC/DC 24, 48 V
For extension modules where the no-
minal voltage is the mains voltage
EN 60204 part 9.1.1 must be fulfilled
AC 0.8 ... 1.1 U
N
DC 0.9 ... 1.2 U
N
DC 0.8 ... 1.1 U
N
5.5 VA; 2.8 W
50 / 60 Hz
approx. 12 mA for K1 and K2
at AC 230 V
approx. 55 mA for K1 and K2
at DC 24 V
7 NO contacts, 1 NC contact for feed
back circuit
35 ms / 35 ms
Relay, forcibly guided
AC 230 / 400 V
DC: see limit curve for arc-free operation
see quadratic total current limit curve
(max. 10 A in one contact path)
3 A / AC 230 V
IEC/EN 60 947-5-1
2 A / DC 24 V
IEC/EN 60 947-5-1
6 A / DC 24 V at 0.1 Hz
10
switching cycles IEC/EN 60 947-5-1
5
6000 switching cycles / h
10 A gL
IEC/EN 60 947-5-1
C10A
10 x 10
switching cycles
6
Continuous operation
- 15 ... + 55 °C
at max. 90 % humidity
- 25 ... + 85 °C
< 2.000 m
4 kV / 2 (basis insulation) IEC 60 664-1
IEC/EN 62 061
Limit value class B
EN 55 011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplastic with V0 behviour
according to UL subject 94
IEC/EN 60 068-2-6
10 ... 57 Hz, 0,075 mm constant
57 ... 150 Hz, 1 g constant
Technical Data
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x height x depth:

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general
use applications"
Switching capacity:
NO contact:
NC contact:
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

CCC-Data

Thermal current I
:
th
Technical data that is not stated in the CCC-Data, can be
found in the technical data section.
nfo

Standard Type

BN 3081.63 AC/DC 24 V
Article number:
• Output:
• Nominal voltage U
:
N
• Width:

Variant

BN 3081.63/61:
with UL-approval
Ordering example for variant
BN 3081.63
/_ _
AC 230 V

Troubleshooting

Failure
LED "K1" does not light up
LED "K2" does not light up

Maintenance and repairs

- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
14
15 / 055 / 04
IEC/EN 60 068-1
EN 50 005
Flat terminals with self-lifting
clamping piece
IEC/EN 60 999-1
Terminal strip removable
DIN rail
DIN/EN 60 715
510 g
100 x 74 x 121 mm
Pilot duty B300
10A 250Vac G.P.
10A 24Vdc
10A 250Vac G.P.
10A 24Vdc
60°C / 75°C copper conductors only
AWG 16 - 14 Torque 0.8 Nm
see quadratic total current limit curve
(max. 5 A in one contact path)
0044207
7 NO contacts, 1 NC contact for
feed back circuit
AC/DC 24 V
100 mm
50/60 Hz
Nominal frequency
Nominal voltage
Variant, if required
Contacts
Type
Potential cause
Power supply A1/A2 not connected
Power supply A3/A4 not connected
BN 3081 / 25.09.18 en / 022A