Note:
The sampling rate of the recorder is fixed at 200 milli seconds by the hardware, i.e.
samples 5 measured data per second.. If the logging speed is set at 1 second in
Instant mode, the recorder logs using the last of five measured data values. For
the same speed in Averaging mode, the recorder logs using the average of the five
measured data values. For the same speed in the Maximum or Minimum mode,
then the recorder logs using the maximum or minimum of the five measured data
values..
Sampling
Instant
200mS
Averaged
200mS
Maximum
200mS
Minimum
200mS
Press Back key to return to real-time display, all configurations will be memorized
Press DI key to select the Digital input. Define the name, Description, and set up the
Event accordingly. Press directional keys• •at the bottom to select the channel.
Press Math key to select the Mathematics input. Except for Expression, it is similar to
do the setting up for Analog input above. Define the name, Description, and select
Type, Log Method, Log Speed, Unit, Scale Low, Scale High, and Event.
Expression column, it appears Source, Operator and a keyboard. The Source covers
all available Analog inputs, Math inputs and Counters. The Operators are Mathematics
functions, details described in 6. Mathematics. Use Source, Operator and keyboard to
define the Math equation. Press directional keys• •at the bottom to select one from 18
available Math. Press Back key to memorize the Math settings.
Logging ( historical trend)
the last of 5 measured data
the average of 5 measured
data
the maximum of 5 measured
data
the minimum of 5 measured
data
81
Display ( real time )
the last of 5 measured
data
the last of 5 measured
data
the last of 5 measured
data
the last of 5 measured
data
Enter