8 Installation
1. Take off frame of room air control.
2. Connect thePPB 30 O to the RLS 45 terminals
FAN1 and FAN 2. Connect PPB 30 K units to
RS 485 bus.
Information
• The power supply to the PPB 30 K (+) MUST
come from the Fan1 or Fan2 connection. Make
connection according to wiring diagram → Con-
nection and wiring diagrams [} 80].
• A combination of PPB30 O and PP 45 units is
not permitted at the FAN1 and FAN2 connec-
tion terminals of the RLS control.
• No exhaust air function is possible for PPB 30
O units on an RLS 45 K control.
• If a PPB 30 K is running in exhaust air mode,
the PP 45 / PPB 30 O units handle the volumet-
ric flow compensation at the fan interface
(Fan1/Fan2). It is important that the unit type +
quantity are set correctly.
3. Insert room air control in the flush-mounted
box and screw down to flush-mounted box
with 2 screws.
4. Fit frame. Ensure that the sensor opening is
above the PP 45 HYI (if fitted) and that the
frame engages.
5. Commissioning ventilation system→ .
8.8 Installing radio switch (EnOcean)
When radio mode is activated, EnOcean radio
components, such as master or slave units or
sensors, can be taught-in directly on ventilation
units. For range of radio components → Technical
data [} 33].
Purely radio-
Combination system
controlled
system
DS 45 RC
RLS 45 K
+
+
PP 45 RC
max. 6
PP 45 RC
PP 45 K
PPB 30 RC
PP 45 O
...
or
max. 3
PPB 30 O /
PPB 30 K
Installation location: Do not mount re-
ceiver, with internal antenna, on wall side of
transmitter.
Purely radio-controlled PP 45 system
1. Simply glue DS 45 RC to installation location
2. Use the "Learn button" to activate teaching-in
3. For basic unit settings, such as "Block Off
PushPull combination system with PP 45 EO
Extension module PP 45 EO can only be com-
bined with PP 45 RC unit pairs. Wired opera-
tion is needed for other unit types.
4. Connect EnOcean extension module to RLS
5. Start up ventilation system, activate in
PP 45 Act EnOcean actuator
With the PP 45 Act EnOcean actuator, radio-con-
trolled PP 45 RC PushPull units can be combined
with wired exhaust air units (ECA, ER). Installa-
tion similar to light switch installation; can be
switched on and off at the touch of a button. For
more information → Accessories instructions.
8.9 Installing PP 45 HYI humidity
sensor in RLS 45 O or RLS 45 K
1. Install room air control as described before.
PP 45 EO
+
PP 45 RC
PPB 30 RC
NOTICE: Unit damage/no function if the hu-
midity sensor is installed incorrectly. Do not
bend pins. Insert sensor up to stop in bush.
on the wall. Alternatively, the radio switch can
also be screwed onto the wall (mounting ma-
terial provided by customer).
mode on the ventilation unit. For more detailed
information on teaching-in → Operating in-
structions.
function" → Installation instructions.
45 K control (RS485)→ Connection and wiring
diagrams [} 80]
EnOcean service mode → .