Maico PPB 30 O Notice De Montage page 46

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

9 Commissioning
Bold
Factory settings
LED flashes quickly
LEDs
46
Ventilation levels
Parameters
Power units (LTs) or
room air controls (RLS)
230 VAC input
PPB 30 K units is taken into
account in another sub-menu
(PPB 30 K parameters)
1
Ventilation level "0" pos-
2
sible
Ventilation level "0" blocked
If ventilation level "0" is set to
blocked, the ventilation units
cannot be switched off at this
control. The units then run
with at least ventilation level
1.
LED flashes slowly
Set value /
Setting /
ventilation level
description
0
Operation without further
1
LTs/RLS
2
Operation with 1 LT or RLS
3
Operation with 2 LTs or RLS
4
Operation with 3 LTs or RLS
5
Slave no. 1
6
Slave no. 2
Slave no. 3
Adjuster for adding further
room air controls (RLS) or
power units (LTs) to this room
air control. Example: Two fur-
ther RLS (RLS #2 and #3) are
connected to RLS #1. Set
value = 2. Set set value 4 on
RLS #2 and set value 5 on
RLS #3.
Notice: Only single-type RLS
combinations are permitted!
1
Sleep mode Intermittent
2
ventilation
3
Safety shutdown
4
Supply air operation without
5
overrun
6
Supply air mode with overrun
time of 6 min.
Supply air mode with overrun
time of 15 min.
For setting an additional func-
tion. This can be activated
with a button or switch at the
230 V input.