J-200
120/240 Volt Convertible Models
A spa connected to a 120 VAC electrical service must be located close
enough to a grounded, grounding-type electrical outlet so that the
included 10 feet (3m) power cord can be plugged directly into it. DO NOT
USE AN EXTENSION CORD as this could cause damage to the spa's
equipment due to insufficient voltage. The power supplied to this spa
must be a dedicated circuit with no other appliances or lights sharing the
power provided by the circuit.
6.0
Power Requirements
Jacuzzi spas are designed to provide optimum performance and
flexibility of use when connected to the maximum electrical service listed
below. Minor circuit board modifications can be performed to allow your
new spa to accept an electrical service other than the factory operation
setting.
Note: Refer to pages 48-51 for circuit board configuration details or
contact your authorized Jacuzzi dealer.
All North American J-210 Convertible Models (60 Hz)
Circuit Breaker:
Number of Wires:
Frequency:
Current Draw:
† In 15A/30A configuration, the heater will not operate while the jets
pump is running in high speed. The factory setting is 120V/15A.
‡ In 40A configuration, remove jumper JP1-2 on the board, to allow the
heater to operate when the jets pump is running in high speed.
CAUTION (For 4-wire 240 VAC Heater Operation): Move the red
wire on the main terminal strip (TB1) from position #1 to position
#3. Make certain wires are connected exactly as shown in Figure
D (Page 16) before applying power. Failure to do so will result in
damage to the circuit board and/or related components and void
the manufacturer's warranty.
12
120V/15A†
30A†, 2-Pole 40A ‡ , 2-Pole
15A†, 1-Pole
3 (15A GFCI
4 (Hard Wire
Cord US
Only*)
60 Hz
12A
240V/40A ‡
240V/30A†
4 (Hard Wire
Only)
60 Hz
21A
Only)
60 Hz
30A