Installation
In order to achieve IP54 rating (NEMA 12) for through-panel mounting, an IP54 insert must
NOTE
be fitted (size 1 and 2). See section 10.7 on page 293. Derating applies when the IP54
insert is fitted. Additionally, the gasket provided should be fitted between the drive and the
backplate to ensure a good seal for the cubicle. If the heatsink mounted braking resistor is
to be used with the drive through-panel mounted, please refer to the Braking Resistor
Installation Sheet supplied with the resistor prior to mounting the drive. For further
information refer to the Unidrive SP User Guide on the CD Rom supplied with the drive.
3.2

Enclosure

Enclosure Layout
Please observe the clearances in the diagram below taking into account any
appropriate notes for other devices / auxiliary equipment when planning the installation.
Figure 3-1 Enclosure layout
AC supply
contactor and
fuses or MCB
Ensure minimum clearances
are maintained for the drive
and external EMC filter. Forced
or convection air-flow must not
be restricted by any object or
cabling
The external EMC filter can be
bookcase mounted (next to the
drive) or footprint mounted (with
the drive mounted onto the filter).
External
controller
Signal cables
Plan for all signal cables
to be routed at least
300mm (12in) from the
drive and any power cable
Unidrive SP Short Form Guide
Issue Number: 2
Electrical
Getting
Menu 0
Installation
Started
Optional braking resistor and overload Locate optional braking
Enclosure
≥100mm
A
www.controltechniques.com
Running
Advanced
the motor
parameters
resistor and overload
external to cubicle
(preferably near to or
on top of the cubicle).
(4in)
A
Note
For EMC compliance:
1) When using an external EMC
2) Power cabling must be at
≥100mm
(4in)
3) Ensure direct metal contact
UL Listing
Diagnostics Appendix
Information
A Size 0 and 1: 0mm (0in)
Size 2 to 6: 30mm (1.181in)
filter, one filter is required for
each drive
least 100mm (4in) from the
drive in all directions
at drive and filter mounting
points (any paint must be
removed)