Installing The Ph100 Photocells; Installing The Fl100 Flashing Light; Electrical Connection To Control Unit - Nice Mhouse SL1S Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

––– STEP 6 –––
6.1 - INSTALLING THE PH100 PHOTOCELLS (fig. 20)
Warning: all installation operations must be performed with the system
disconnected from the power supply; if fitted, the PR1 backup battery
must also be disconnected.
Warnings: Take care not to damage the o-ring fitted (fig. 20-3) [A].
Select the position of the two elements making up the photocell (TX and
RX) observing the following:
• Place them at a height of 40-60 cm from the ground, to the sides of the
zone to be protected, and as close as possible to the edge of the gate,
i.e. no further than 15 cm.
• There must be a raceway tube at the point envisaged for routing cables.
• Point the transmitter TX at receiver RX with a maximum tolerance of 5°.
01. Remove the front glass panel (fig. 20-1).
02. Position the photocell at the point where the cable routing tube
arrives.
03. Trace the drilling points using the base as a reference. Use a percus-
sion drill to drill the wall, with a 5 mm tip, and insert 5 mm plugs.
04. Route the electric cables through the specific holes (pierce those
required): see fig. 20-2.
05. Fix the base, using the relative screws [B] of fig. 20-3 ensuring that
the hole on the base [C] of fig. 20-3 is aligned with the cable outlet.
2 self-tapping screws are also supplied for fixture on surfaces with a
different density.
06. Connect the electrical cable in the relative terminals of both TX and
RX (fig. 20-4). From an electrical point of view, TX and RX must be
connected in parallel (fig. 20-5) and to the blue terminal of the con-
trol board. No polarity needs to be observed.
07. Fix the covering shell [D] of fig. 20-6 with the two screws [E] of fig.
20-6 using a Phillips screwdriver. Lastly, insert the external cover [F]
in fig. 20-6 pressing it slightly to secure in place.

6.2 - INSTALLING THE FL100 FLASHING LIGHT

FL100 (fig. 21)
Select the position of the flashing light so that it is in the vicinity of the
gate in a visible location; it can be fixed on either a horizontal or vertical
surface; fig. 21 shows the two options:
01. Remove the cover, unscrewing the screw if present.
02. Separate the base, unscrewing the screws present to route the elec-
tric cables.
03. Trace the drilling holes using the base as a reference and ensuring
that the hole on the base is aligned with the cable outlet. vertical
fixture (A) or horizontal fixture.
04. Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6
mm plugs.
05. Fix the base, using the relative screws.
06. Connect the electric cables in the relative FLASH and "aerial" termi-
nals as shown in the figure: To facilitate operations, remove terminals,
make connections, then refit the terminals.
No polarity needs to be observed on the FLASH terminal, while in the
case of the shielded cable connection of the aerial, the sheath must
be connected.
07. Insert the lamp holder in the base, taking care to press it down so
that it locks into place;
08. Secure the body of the flashing light to the fixing support and turn it
left until it clicks into place, then secure by means of the screw.
10

6.3 - ELECTRICAL CONNECTION TO CONTROL UNIT

01. Remove the lateral cover of the gearmotor: remove the screw and
pull the cover upwards (fig. 22);
02. Depending on the position of the gearmotor (right or left), set the
electric jumper for the direction of the opening manoeuvre (Open),
see fig. 23;
03. Remove the rubber membrane of the hole made for insertion of the
electric cables. Insert the cables required for connection of the vari-
ous devices(fig. 24). Leave cable lengths of at least 40-50 cm.
04. From the rubber membrane, remove a sufficient part of the internal
mesh for insertion of the cables. Then fit the membrane into its seat
(fig. 25).
05. At this point, make the electrical connections of the various devices
to the control unit terminals (see fig. 26 and following paragraphs).
• The terminals have the same colour as the terminals on the cor-
responding devices; for example the grey terminal (OPEN) of the
KS100 key-operated selector switch must be connected to the grey
terminal (OPEN) of the control unit;
• No polarity is needed for virtually any of the connections; only in the
case of the shielded cable of the aerial, the central core and sheath
must be connected as shown in detail [A] of fig. 26.
Notes: - To facilitate connections, terminals can be removed as
shown in fig. 27 - [A]; after making the connections, refit the ter-
minals in their seats. - At the end of connections, use cable ties to
secure the electric cables to the relative fixtures (fig. 27 - [B]).
06. Close the lateral cover of the gearmotor as shown in fig. 28.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mhouse sl10s

Table des Matières