minimum clearance to combustibles and non-combustibles

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM APPLIANCE AND VENT
SURFACES:
-
0" (0mm) to wall mounting plate fl anges
-
1" (25.4mm) to bottom and sides of vent pipe for horizontal runs*
-
3" (76.2mm) to top of vent pipe for horizontal runs*
MINIMUM CLEARANCES TO COMBUSTIBLES (FROM THE APPLIANCE) :
-
15" (38.1cm) to top/ceiling
-
7" (177.8mm) to sides
-
6"
(152.4mm) to bottom/fl oor
* On all vertical vent rises, only one inch clearance to the vent pipe is required.
15" (38.1cm)
MIN.
5.5" (139.7mm) MIN.
36"
(91.4cm)
MAX.
ALCOVE
INSTALLATION
SIDE VIEW
7"
(177.8mm)
MIN.
36"
(91.4cm)
MAX.
INSTALLATION
TOP VIEW
6" (152.4mm) MIN.
7"
(177.8mm)
MIN.
ALCOVE
15" (38.1cm)
5.5" (139.7mm) MIN.
installation
MIN.
6" (152.4mm) MIN.
TYPICAL
INSTALLATION
W415-1673 / A / 10.07.19
EN
23