Installation of the gland in the enclosure.
Conditions for threaded and unthreaded holes
Tolerance Class (6H) is required for Ex d and
Enclosure
Material
Limitations
Enclosure
interface
sealing method
Maximum
surface
roughness of
the enclosure
wall
Thickness
range for the
enclosure
wall (t)
Perpendicularity +/–1° or 0,2 mm at the
Permitted use
and location of
any earth tags
For chamfered
holes
Lock nuts
Any thread sealant should be non-hardening.
It is the users/installers responsibility to ensure that the
interface between the enclosure and cable gland is suitably sealed
for the required application.
If required an anti-seize lubricant then ensure no lubricant
comes into contact with the cable gland seals as this may impair
performance.
DE, FR, RU: Page 23-25
Threaded Holes
recommended for Ex e is
max 6G/6H. Ref. ISO 965-1
and ISO 965-3.
Brass glands should not
be installed in zinc or
aluminium enclosures
outdoor or in humid
environments.
If the sealing surfaces are
uneven, use PTFE washer
NFWM25 or the green fiber
washer GFWM25 (washers
to be ordered separately).
Ra 6,4µm, better than 3,2µm
is recommended.
≥ 4 mm. For Ex db
applications a minimum
of 5 fully engaged threads
is required. The thread will
maintain an IP rating of
IP64. A sealing washer shall
be used to maintain all IP
ratings ≥ IP64.
outer edge of the gland,
whichever is smaller.
Earth tags should be
installed on the inside of
the enclosure. Thickness
of tag and lock nut to
be considered when
determining the min/max
wall thickness of the box.
The outermost edge must
not have a greater diameter
than the center of the
washer.
Only use nVent RAYCHEM
locknuts or other types
recommended by the
manufacturer.
Unthreaded (through) holes
Nominal thread size M25
–0,0mm/ +0,7mm (M).
Brass glands should not
be installed in zinc or
aluminium enclosures
outdoor or in humid
environments.
If the sealing surfaces are
uneven, use PTFE washer
NFWM25 or the green fiber
washer GFWM25 (Washers
to be ordered separately).
Ra 6,4µm, better than 3,2µm
is recommended.
Minimum wall thickness:
Plastic boxes ≥ 2 mm
Metal boxes ≥ 1 mm but
less than the thread length
of the cable gland + the
thickness of the locknut.
+/–1° or 0,2 mm at the
outer edge of the gland,
whichever is smaller.
Earth tags should be
installed on the inside of
the enclosure. Thickness
of tag and lock nut to
be considered when
determining the min/max
wall thickness of the box.
The outermost edge must
not have a greater diameter
than the center of the
washer.
Only use nVent RAYCHEM
locknuts or other types
recommended by the
manufacturer.
nVent.com/RAYCHEM | 19