p-c, p-v and p-T control modes:
Duty point on
maximum curve
Duty point within
the control range
Adjustment range H
Installation and operating instructions Siriux/Siriux-D
p-c (Fig. 9)
Draw from duty point towards the left.
Read off setpoint H
S
this value.
Draw from duty
point towards the
left. Read off set-
point H
and set the
S
pump to this value.
H
see
,
min
max
5.1 Type key
p-v (Fig. 8)
and set the pump to
Go along the control
curve up to the max-
imum curve, then
move horizontally to
the left. Read off the
setpoint H
and set
S
the pump to this
value.
p-T (Fig. 10)
The settings are to be
made by customer
service taking the plant
conditions into
account, via the serial
digital interface or
using an IR operating
and service unit
(accessory).
T
: 20 ... 100 °C
min
T
: 30 ... 110 °C
max
T = T
 10 °C
-T
max
min
Gradient:
Hs/T  1 m/10 °C
H
H
,
min
max
Adjustment in
positive effective
direction:
 H
H
max
min
Adjustment in
negative effective
direction:
 H
H
min
max