English
• Menu of IF Modules with bus function:
LC display
78
Setting
Signal for the building management system (BMS)
"Id" (Identification number) appears on connected
IF Modules with serial digital interface, for sending
a signal to the building management system (for
servicing or for commissioning the building auto-
mation (BA)).
If the control button is turned, the Id
indicator flashes
The Id signal is sent to the building
management system.
The display opens the next menu.
If no signal is output, the control button can be
turned until the Id indicator no longer flashes.
Pressing the button opens the next menu on the
display
Setting the bus address
"OFF": bus communication is switched off
appears on the display indicating
communication via serial data interface.
Turn the control button to select a BUS
address (e.g. 64).
The address range depends on the bus
system used (see corresponding Instal-
lation and operating instructions)
The setting is applied
The display opens the next menu